vertical flame test chamber - Qinsun
Produttore di strumenti di prova professionali
Hotline nazionale di consultazione:+86 021-64208466
Prodotti

camera di prova verticale della fiamma

The Vertical Flammability Chamber, designed for American Standards, measures the vertical flame spre

WhatsApp: +86 13816217984

Email: info@qinsun-lab.com

Contenuto
The Vertical Flammability Chamber, designed for American Standards, measures the vertical flame spread for children's sleepwear, fabrics, other textile materials or resilient filling materials used in upholstered furniture.
 G233

Applicazione:
The vertical burning of textiles is suitable for all types of fabrics and their products. Test method applicable to the burning performance of the bottom edge of the vertical textile specified in GB5455-2014 standard.
 
Caratteristiche:
Gas pipeline system special designed, low space occupied, and convenience to move;
Exhaust vents at the bottom and top of test chamber ensure good ventilation and steady flame;
LED displayer shows the igniting time, afterflame time and afterglow time, with high working efficient and the data more accuracy;
A stainless steel construction, large glass-viewing window;
Excellent reliability and minimum maintenance;
Purpose-designed test chamber.
 
Norme:
ASTM D6413, CALIF TB117, DOC-FF 3/71, 16CFR Parts1615/1616, FTMS 191-5903, CPAI 84     
 
parametro:
Articolo
Parametro
Inner size
About 330*330*765mm.
Windows
tempered glass observation window
Exhaust holes
16pcs proof holes,6pcs each side(total 12pcs)
Exhaust diameter
12.5mm
Proof hanging clamp
located 17mm above the highest point of the igniter nozzle.
Diameter of the igniter nozzle
11mm
Angle about the head and vertical line
25°
inlet gas pressure of the igniter
17.2kpa±1.7kpa
Ignition time
accurate to 0.05s
Gas source
industrial grade propane, butane or propane / butane mixed gas. When the sample is pretreated according to 7.3 in GB5455-2014, methane gas with a purity of not less than 97% is selected.
Dimensione del campione
300*89mm, five horizontal and vertical
Temperatura ambiente
-10 ° C ~ 30 ° C
Tensione di alimentazione
220V±10% 50HZ
Potenza
less than 100W
Flame time
0-99M99S
Flame time accuracy
± 0.01s
Afterglow time
longest 0-99M99S
Blue flame height
15mm-175mm with flame height scale
Ignition time
any setting (can be preset)
 

Disclaimer: Il contenuto di cui sopra è per riferimento e comunicazione solo tra addetti ai lavori del settore e non garantisce la sua accuratezza o completezza. Secondo le leggi e i regolamenti pertinenti e i regolamenti di questo sito web, le unità o le persone fisiche che acquistano articoli correlati devono ottenere qualifiche e condizioni di qualificazione valide.